Models S70X and S8xx Viewing Heads

FLAME SCANNER VIEWING HEAD FOR FLAME MONITORS

GENERAL DESCRIPTION
MODELS S702, S702 PF, S702 HF, S702 HF PF, S706, S706 PF, S802, S802 HF, S806

The IRIS Models S7xx and S8xx series of Viewing Heads are compact cylindrical units that are easily detachable from their Delrin mountings.

A 1/2 inch NPT female pipe thread is provided on the mounting for attaching a swivel mount or sight pipe. Provision for purge air is by means of a 1/4 inch female pipe thread on the side of the mounting. A continuous flow of purge air is required for cooling.

A transparent Hirshmann connector with two LED's and 15 ft. length of  four conductor shielded cable is provided as standard is provided with all viewing heads, except for the -PF model. The LED's assist in set-up and self checking of the viewing head.

Accommodation is provided for an orifice and snap ring in the mounting block.

MODELS / FEATURES
  • Model S702 
    IR Viewing head with connector and 15 ft. cable
     
  • Model S702 HF
    IR Viewing head  with high frequency filter, connector and 15 ft cable
     
  • Model S706
    UV Viewing head with connector and 15 ft cable
 
Viewing Head for flame monitor Model S70X
 
  • Model S702 PF
    IR Viewing head with 1/2 NPT and 20 inch cable attached
     
  • Model S702 HF PF
    IR Viewing head with High Frequency filter and 1/2 NPT and 20 inch cable attached
     
  • Model S706 PF
    UV Viewing head with 1/2 NPT and 20 inch cable attached
 
Viewing Head for flame monitor Model S70XPF
 
  • Model S 802
    IR Viewing head with connector and 15 ft. cable
     
  • Model S802 HF 
    IR Viewing head  with high frequency filter, connector and 15 ft cable
     
  • Model S806
    UV Viewing head with connector and 15 ft cable
 
Viewing Head for flame monitor Model 80X
APPROVALS:
The IRIS Model 700 and 800 Viewing Heads are certified by FM (Factory Mutual) and CSA (Canadian Standards Association) for Class I, Div. 2, Groups A, B, C, & D for hazardous location applications.
SPECIFICATIONS: MODELS S7xx and S8xx VIEWING HEADS
ELECTRICAL Input Power 22VDC to 26VDC, 70 mA MAX from Signal Processor
 
ENVIRONMENTAL Viewing Head Sealing NEMA TYPE 4/4X with tightened connector and UV cable protection
Ambient Temperature -40°F to 185°F (-40°C to 85°C)
 
IR DETECTOR SPEC
(S702, S702-PF, S702-HF,
S702-HF-PF, S802, S802-PF)
Detector type Germanium photodiode with spectral response 1110 to 1660nm (1/2 intensity points)
High Pass Filter Pickup 33 Hz standard, 155 Hz High Freq. option (-HF)
OPTICAL: Angle of view 1 degree (1.45? dia. at 6 ft.)
 
UV DETECTOR SPEC
(S706 & S706-PF, S806)
Detector Type UVtron with spectral response 185 to 260nm
OPTICAL: Angle of view 5 degrees (1 inch per foot)
 
CABLE & CONNECTOR Signal Processor to Viewing Head Transparent Hirshmann connector with LED's and 4 conductor, #22 AWG cable with shield. Standard length of 15 ft. or length to suit
-PF model or when extending standard cable Use 4 conductor, #20AWG with braided shield, 95% coverage. Shield must be grounded at both ends of cable.
 
 
Send mail to flame@iris-systems.com with questions or comments about this web site.
 Copyright © 2006 Iris Systems Inc. 7583 Vantage Place, Delta BC. V4G 1A5
 Last Updated on 02/14/2006
 
 IRIS Signal Processors, Flame Monitors, Viewing Heads and Flame Detectors are made in the USA